Every temperature loop needs something to turn a Pt100 resistance or a thermocouple millivolt into a signal the PLC can read. Where you put that converter, and what it must do besides converting, decides which SENECA model to order.

1. The four places a converter can live
| Location | SENECA model | Key specs | Choose it when |
|---|---|---|---|
| In the sensor head | T121 | Pt100 (−200 to +650 °C), Pt500, Pt1000, Ni100, thermocouples J K R S T B E N, mV, potentiometer; 2-wire 4–20 mA, 7–30 V loop; 1,500 Vac isolation; 0.1 %; ambient −40 to +85 °C; Ø43.7 × 20 mm; configured with Easy-LP software | The sensor is far from the panel: two wires carry a current signal that does not care about cable resistance, and the mV or ohm signal never leaves the head |
| On the DIN rail, powered by the loop | K121 | Same input families plus Cu50/Cu100, Ni120/Ni1000, ±30 V, ±24 mA and 0–400 Ω; passive 4–20 mA out; 7–30 Vdc from the loop; 1.5 kVac 2-way; 16-bit, 0.1 %; 6.2 mm; ATEX II 3G / II 3D (Zone 2 / 22) | The PLC or DCS card supplies loop power, there is no 24 V in the field cabinet, or the cabinet sits in a Zone 2 area |
| On the DIN rail, 3-way isolated with a voltage option | K109PT | Pt100 in; 0–10 V, 0–5 V or 4–20 mA out; three-way isolation; 6.2 mm | The receiver wants 0–10 V (many drives, chillers and HVAC controllers), or you need input, output and supply isolated from each other |
| On the DIN rail, universal with a limit relay | Z109REG2-1 | TC J K R S T B E N, Pt100/500/1000, Ni100, mA, 75 mV–20 V, potentiometer; isolated analog out; one SPST alarm relay; 10–40 Vdc or 19–28 Vac; 0.1 %; microUSB configuration | Mixed sensor types on one site and you want one spare, or you need a local high-temperature trip without PLC logic |
| Straight to the network | Z-4RTD2 | 4 RTD inputs, Modbus RTU, 14-bit, 17.5 mm | Many temperatures going to SCADA or a data logger; skip the 4–20 mA stage entirely |
2. Specification details that cause call-backs
- 3-wire vs 4-wire Pt100. Two-wire RTD connections add the cable resistance to the reading: 10 m of 1.5 mm² cable adds about 0.24 Ω, which is 0.6 °C. Use 3-wire as a minimum; the T121 and K121 accept 2-, 3- and 4-wire.
- Cold-junction compensation. Thermocouple converters compensate at their own terminals. A T121 in the head does this at the sensor; a DIN converter does it in the cabinet, so the thermocouple extension cable must run all the way to the cabinet in the correct compensating wire. Mixing copper cable into a thermocouple run is the most common cause of a 5–10 °C error.
- Burn-out direction. Configure the output to go upscale or downscale on sensor break and make sure the PLC alarm matches it. The Z109REG2-1 and K121 both offer selectable burn-out.
- Ambient temperature. A transmitter in a sensor head on a steam line sees far more than 65 °C in summer. The T121 is rated to +85 °C; standard DIN converters are rated to +65 °C.
- Response time. Head-mount and loop-powered converters respond in under 620 ms for RTD and thermocouple inputs; the sensor sheath itself is usually slower, so this rarely matters, but it does for thin-wire thermocouples in control loops.
3. Three worked examples
Boiler feed-water header, 60 m from the panel, Pt100 in a thermowell. T121 in the head with 3-wire Pt100, 4–20 mA over the existing two-core instrument cable to the PLC. Nothing to add in the cabinet.
Paint-shop oven in a Zone 2 area, eight type K thermocouples. Eight K121 on the rail of the Zone 2 cabinet, powered by the DCS loop supply, 6.2 mm each, 50 mm of rail in total, ATEX certificate in the project file.
Cold-storage warehouse, 24 Pt100 sensors to a SCADA. Six Z-4RTD2 modules on one RS-485 line to a Z-KEY gateway, no transmitters, no analog input cards; one Z109REG2-1 on the compressor discharge with the relay wired to the alarm beacon.
4. Ordering information to include
- Sensor type and wiring (Pt100 3-wire, type K, etc.) and the measuring range you want to map to 4–20 mA.
- Where the converter will be mounted and the ambient temperature there.
- Output required by the receiver: 4–20 mA, 0–10 V, Modbus.
- Whether the loop is powered by the receiver (then choose K121 or T121) or by a cabinet supply.
- Hazardous-area classification, if any.
We configure the converters before shipping, so the range and burn-out direction are already set when your technician wires them.
Get a quote for this application
Email your sensor list with ranges and the receiver type – we return the model list, pre-configuration sheet and price within one business day.
Quick answers
Can a T121 be mounted on a DIN rail instead of in the head?
Yes, with the DIN rail adapter; but at that point the K121 is usually the better buy because it has the same inputs and a wider range of ranges.
Which converter gives 0–10 V from a Pt100?
The K109PT: Pt100 in, 0–10 V or 0–5 V or 4–20 mA out, three-way isolated.
Do I need an isolator as well as a converter?
No. All four converters are galvanically isolated (1.5 kVac); the K109PT and Z109REG2-1 additionally isolate the supply from both input and output.
How are the ranges set?
T121 with Easy-LP, K121 with EASY SETUP over USB, Z109REG2-1 with EASY SETUP over microUSB or the Android app. We can set them for you before shipping.