Danfoss · Variable Frequency Drives
VLT AQUA Drive FC 202 15 kW
Part number FC-202P15KT4E20H2XGXXXXSXXXXAXBXCXXXXDX
Dedicated water and wastewater drive, 15 kW, 3 × 380–480 V, cascade pump controller, flow compensation, dry-run and pipe-fill functions, Modbus and BACnet.
- CE
- UL
- IP20/IP55
- Modbus

Overview
The VLT AQUA Drive FC 202 is Danfoss's dedicated drive for water and wastewater applications from 0.25 kW to 1.4 MW. Its application features cover what a pump station needs without a PLC: cascade control of up to six pumps, flow compensation of the setpoint, sleep mode with boost, dry-run and end-of-curve detection, pipe-fill mode to avoid water hammer, and a deragging function for wastewater pumps. Energy monitoring and the Smart Logic Controller add sequencing and alarms. The drive is available in IP20, IP21, IP55 and IP66 enclosures with optional RFI filters and harmonic filters; the example type code is a 15 kW 400 V IP55 unit. Modbus RTU and BACnet are standard; PROFINET and EtherNet/IP are options.
Key features
- 0.25 kW–1.4 MW; water-specific functions: cascade control, flow compensation, pipe fill, dry-run, deragging
- Sleep mode with boost, end-of-curve detection, energy log — no PLC needed for pump stations
- Enclosures IP20/21/55/66 with coated boards; 50 °C ambient; built-in DC-link reactors
- Modbus RTU and BACnet MS/TP standard; PROFINET, EtherNet/IP, PROFIBUS options
- VVC+ and flux vector control for IM and PM motors; up to 98 % efficiency
Typical applications
- Clean-water booster and distribution pumps
- Wastewater lift stations and aeration blowers
- Irrigation and industrial water supply
- Cooling-water and chiller pumps
Technical specifications — FC-202P15KT4E20H2XGXXXXSXXXXAXBXCXXXXDX
| Ratings | |
|---|---|
| Power | 15 kW / 20 HP (series 0.25 kW–1.4 MW) |
| Supply | 3 × 380–480 V AC |
| Output current | 32 A normal overload (110 % for 60 s) |
| Efficiency | ~98 % |
| Control | |
| Control modes | U/f, VVC+, flux vector (IM and PM motors) |
| Application functions | Cascade (6 pumps), flow compensation, pipe fill, sleep, dry-run, deragging |
| I/O | 6 DI, 2 AI, 1 AO, 2 relays; expandable |
| Communication | Modbus RTU, BACnet MS/TP standard; PROFINET, EtherNet/IP, PROFIBUS options |
| Construction | |
| Enclosure | IP55 (IP20/21/66 available) |
| Harmonics | DC-link reactors built in; AHF/LHD filters optional |
| RFI filter | Class A1/B option |
| Environment | |
| Ambient temperature | -10…+50 °C |
| Approvals | CE, UL, cUL, C-Tick |
Specifications are summarised from the manufacturer's documentation for selection purposes. Always confirm against the current datasheet before design-in; we send the datasheet and the exact ordering code with every quotation.
Related part numbers and alternatives
| Part number | Relationship | |
|---|---|---|
FC 102 | VLT HVAC Drive FC 102 — same platform for building services | Quote |
FC 302 | VLT AutomationDrive FC 302 for general industrial duty | Quote |
ACS580-01 | ABB alternative with pump functions | Quote |
Not sure which variant you need? Send us the nameplate photo or the old part number and we will identify the current equivalent.
Supply, documentation and lead time
What you receive
- Genuine Danfoss product in original packaging
- Commercial invoice and packing list; Certificate of Conformance on request
- Datasheet, declaration of conformity and country of origin as issued by the manufacturer
- Manufacturer warranty, period stated on the quotation
How we quote
- Reply within one business day with price, lead time and stock position
- Alternatives proposed when they improve price or delivery
- Incoterms of your choice: EXW Hai Phong, FOB/FCA, CIF/DAP to your site
- Consolidated shipments for multi-line orders; export documentation for buyers outside Vietnam
Indicative HS code 8504.40 — final classification is confirmed on the commercial invoice.
Frequently asked questions
Can the FC 202 control several pumps without a PLC?
Yes. The built-in cascade controller runs up to six pumps (fixed-speed via contactors or variable-speed with additional drives) on a pressure or flow setpoint with lead/lag alternation.
What is deragging?
A function for wastewater pumps that reverses and cycles the impeller on a schedule or when a torque increase is detected, clearing rags before they block the pump.
Is the FC 202 available from stock, and what is the lead time?
Standard IP20/IP55 ratings to 90 kW are typically 2–4 weeks; large frames and harmonic filters longer. We confirm with the quotation.