Genuine industrial components · Technical selection support · Export documentation+84 879 848 668 · sales@hoantrantdh.com

Turck · Flow Meters

FCS-G1/2A4-AP8X-H1141 Flow Monitor (Calorimetric)

Part number FCS-G1/2A4-AP8X-H1141

Calorimetric immersion flow monitor for liquids, G1/2 stainless probe, 1–150 cm/s detection, PNP output with teach-in, M12, for cooling-water and pump dry-run monitoring.

  • CE
  • IP67
  • PNP
  • Immersion
Turck FCS-G1/2A4-AP8X-H1141 Flow Monitor (Calorimetric) (FCS-G1/2A4-AP8X-H1141) — product card

Overview

The Turck FCS-G1/2A4-AP8X-H1141 is a compact calorimetric flow monitor: a stainless-steel probe with a G1/2 thread inserted into the pipe detects whether liquid is flowing, switching a PNP output when flow drops below the taught threshold. The sensor has no moving parts, is independent of pipe size and is used mainly for cooling-water monitoring on welding guns, spindles and lasers, and for dry-run protection of pumps. Setup is by teach-in with the potentiometer or keys, and the LED chain shows the flow relative to the switch point. Versions for gases, with 4–20 mA output (FCS-...-LIX) and with integrated temperature measurement are available in the FCS/FCI family.

Key features

  • Calorimetric principle, no moving parts, independent of pipe diameter
  • Detection range 1–150 cm/s for water; teach-in switch point; LED flow indication
  • PNP NO output 400 mA, 19.2–28.8 V DC; M12 connector
  • G1/2 stainless probe (316 Ti), 24 mm immersion; medium -20…+80 °C; 100 bar
  • IP67 housing; variants with 4–20 mA, temperature output or for gases

Typical applications

  • Cooling-water flow monitoring on welding and laser equipment
  • Dry-run protection of pumps
  • Lubrication and hydraulic circuit monitoring
  • Flow/no-flow detection in process lines

Technical specifications — FCS-G1/2A4-AP8X-H1141

Measurement
PrincipleCalorimetric
Detection range1–150 cm/s (water)
MediumLiquids (gas version available)
Response time2–10 s typical
Temperature gradient≤ 0.4 K/min
Output
OutputPNP NO, 400 mA
AdjustmentTeach-in / potentiometer
IndicationLED chain, flow relative to set point
Power19.2–28.8 V DC
Process
Process connectionG1/2
Probe316 Ti stainless, 24 mm
Medium temperature-20…+80 °C
Pressure100 bar
Environment
Ambient temperature-20…+70 °C
ProtectionIP67
ConnectionM12 × 1, 4-pin

Specifications are summarised from the manufacturer's documentation for selection purposes. Always confirm against the current datasheet before design-in; we send the datasheet and the exact ordering code with every quotation.

Related part numbers and alternatives

Part numberRelationship
FCS-G1/2A4-LIX-H1141Version with 4–20 mA analog outputQuote
FCS-G1/2A4-AP8X-H1141/D100Version for gasesQuote
SM6000ifm magnetic-inductive meter when flow rate is neededQuote

Not sure which variant you need? Send us the nameplate photo or the old part number and we will identify the current equivalent.

Supply, documentation and lead time

What you receive

  • Genuine Turck product in original packaging
  • Commercial invoice and packing list; Certificate of Conformance on request
  • Datasheet, declaration of conformity and country of origin as issued by the manufacturer
  • Manufacturer warranty, period stated on the quotation

How we quote

  • Reply within one business day with price, lead time and stock position
  • Alternatives proposed when they improve price or delivery
  • Incoterms of your choice: EXW Hai Phong, FOB/FCA, CIF/DAP to your site
  • Consolidated shipments for multi-line orders; export documentation for buyers outside Vietnam

Indicative HS code 9026.10 — final classification is confirmed on the commercial invoice.

Frequently asked questions

Does the FCS measure the flow rate?

The standard AP8X version is a flow monitor: it switches above or below a taught flow velocity. For an analog flow signal choose the LIX version, or a magnetic-inductive meter for accurate volume flow.

How long does it take to react when flow stops?

Calorimetric sensors respond within a few seconds; the exact time depends on the medium and the difference between set point and actual flow. For pump protection this is normally sufficient.

Is the FCS-G1/2A4-AP8X-H1141 available from stock, and what is the lead time?

Typically 1–2 weeks from Turck regional stock. We confirm with the quotation.

Send us a part number, a BOM or a drawing.

Our engineers reply within one business day with availability, lead time and alternatives where they save you cost or time.

ZaloCallEmail