Short answerSchneider Electric ended commercialization of Modicon Quantum processors on 1 December 2018, Quantum Safety on 1 December 2019 and Quantum I/O on 1 December 2021, according to its official change notice. Plants still running Quantum should hold tested spares of every critical 140-series module, keep Unity Pro / Control Expert or Concept project backups, and plan a CPU-first migration to Modicon M580, which Schneider states is compatible with existing Quantum I/O. HOANTRANTDH sources verified new and refurbished 140-series parts and ships across ASEAN and worldwide.

What Schneider officially announced

In its Red Flag Change Notice for Modicon Quantum PACs (December 2016), Schneider Electric published these end-of-commercialization dates:

  • Quantum processors (CPUs): 1 December 2018
  • Quantum Safety processors and I/O: 1 December 2019
  • Quantum I/O: 1 December 2021

The same notice points customers to the Modicon M580 ePAC as the upgrade path and states that M580 is compatible with existing Quantum I/O. After commercialization ends, new units are no longer supplied through the normal channel, and repair or exchange support is limited in time. Always confirm the current lifecycle status of each exact part number with Schneider or your distributor before planning.

Why Quantum is still everywhere

Quantum was Schneider’s flagship large PLC for two decades. It still runs water and wastewater plants, power stations, cement kilns, mining conveyors, oil and gas facilities and large building systems across Asia, the Middle East, Africa and Latin America. Many of these installations are stable and well understood, so owners delay replacement until a failure forces the decision. The risk is that the failure arrives before the spare.

Modules that most often stop a Quantum system

  • Power supplies (140 CPS series): electrolytic capacitors age with heat; a failed supply takes down the whole rack.
  • CPUs (140 CPU series): battery, memory and communication port failures; firmware version must match the application and programming software.
  • Communication modules: Ethernet (140 NOE / NOC), Modbus Plus (140 NOM) and remote I/O heads (140 CRP / CRA). Networks built on Modbus Plus are especially exposed because spare adapters and cards are scarce.
  • Analog and discrete I/O (140 ACI, ACO, DDI, DDO, DAI, DAO…): individual channels fail first; keeping one spare of each module type usually covers several racks.
  • Backplanes and terminal strips (140 XBP, 140 XTS): rarely fail, but needed when a rack is damaged.

How to verify a used or refurbished Quantum module

  • Match the full part number and hardware revision on the label, not only the family name.
  • Check CPU and communication firmware against your Unity Pro / Control Expert or Concept version before installing.
  • Bench test on a powered rack: power-up diagnostics, I/O channel test, and for communication cards a live Modbus/Ethernet session.
  • Inspect for heat discoloration, corrosion, bent backplane pins and replaced components.
  • Ask for test records and a written warranty; avoid unbranded “new” units with no traceability.

Migration paths that limit downtime

  1. CPU-first upgrade to M580: Schneider positions M580 as compatible with existing Quantum I/O, which lets you replace the obsolete processor layer first and keep field I/O and wiring in place for a later phase. Use Schneider’s Quantum-to-M580 transition matrix to confirm each module.
  2. Software conversion: applications built in Unity Pro move to EcoStruxure Control Expert. Older Concept or ProWORX projects need conversion first, so budget engineering time for logic review and testing.
  3. Phased rack replacement: replace one rack or one process area at a time during planned shutdowns, using wiring adapters where available so field terminations are not disturbed.
  4. Bridge with spares: where budget for migration is not yet approved, a spares stock sized to the installed base keeps the plant safe while the project is prepared.

Recommended spares policy for Quantum users

  • At least one spare power supply and one spare CPU of each type in use, tested and with the correct firmware.
  • One spare of every communication module type, especially Modbus Plus and remote I/O heads.
  • One spare of every I/O module type per site; more if the same type is used in many racks.
  • Current project backups stored off the PLC, plus a working programming PC and cable.
  • A written migration plan with an estimated budget, so the decision is ready when a major failure occurs.

How HOANTRANTDH helps

We source new, new-surplus and refurbished Modicon Quantum modules through more than 35 countries, test them before shipping, and supply them with warranty. Our engineers can review your installed base, propose a spares list and outline an M580 migration. Browse our Schneider Electric parts catalog, read the obsolete automation parts sourcing guide, or compare with Siemens S7-300 and S5 end-of-life options.

Request a quote or a site assessment

Tell us your plant location, the equipment or part numbers concerned, and your timeline. An engineer replies within 48 business hours in English.

Or email sales@hoantrantdh.com · PlusSmart ASEAN: hoan.tran@plussmart.tech

Cần báo giá hoặc tư vấn kỹ thuật?

Để lại thông tin, kỹ sư HOANTRANTDH sẽ liên hệ trong giờ làm việc.

Hoặc gọi/Zalo 0879 848 668 · Email sales@hoantrantdh.com